PIMS aag report: Executive Director Imran Sikandar sameet 8 ahalkar muattal

Aarzi inquiry mein saamne aaya ke nursery ke liye inkhila ka koi mansooba maujood nahin tha, nikasi ke darwazon par tale lage hue thay aur emergency services ko bulane mein 16 minute guzar gaye, jis par Executive Director Imran Sikandar aur 7 deegar ahalkar muattal kar diye gaye. Faujdari karwai ka hukm diya gaya hai. Mukammal report ab public kar di gayi hai.

Raaye dein

Tarjuma ho raha hai… 3 / 10 Asal tehreer parhein

PIMS Executive Director Imran Sikandar and 7 others suspended after an inquiry found no evacuation plan, locked exits, and a 16-minute delay before emergency services were called. — FILE/THE THURSDAY TIMES
PIMS ke Executive Director Imran Sikandar aur 7 doosre ahalkar muattal kar diye gaye, jab inquiry mein saamne aaya ke imarat khali karwane ka koi mansooba nahin tha, nikasi ke darwazon par tale lage hue thay, aur emergency services ko ittila dene mein 16 minute ki der hui. — File/The Thursday Times

ISLAMABAD (The Thursday Times) — PIMS Hospital mein pichhle hafte lagne wali aag ki antrim tehqeeqat ke zariye tarteeb di gayi CCTV timeline se zahir hota hai ke nawzaida bachchon ki nursery mein musibat ki pehli alamat se le kar poori tarah dhuen se bhar jane tak do minute se bhi kam waqt laga. Yeh baat 29 August ko Wazir-e-Azam Shehbaz Sharif ko pesh ki gayi committee ki report mein kahi gayi hai. Report se yeh bhi saamne aata hai ke isi hospital mein pehle lagne wali aag ki aik alag tehqeeqat nursery mein aag lagne se sirf aik din pehle bhi nazar-e-sani ke liye wapas bheji ja rahi thi.

28 August ki tareekh wali antrim report, jis par committee ke chairman aur sabiq wafaqi secretary Shahid Khan ke saath arkan Irfan Nawaz Memon, Barrister Nabeel Ahmed Awan aur Major General (Retired) Dr. Khurshid Uttra ke dastkhat hain, CCTV footage ki madad se 26 August ki subah ko minute ba minute tarteeb deti hai. Charge Nurse Nasreen subah 6:38:15 par nursery se madad mangte hue bahar aati nazar aati hain. Woh aur Security Guard Maria 6:38:35 par andar jati hain, jab tak shoalon ke aks pehle hi nazar aane lagte hain. Staff Nurse Razia 6:38:56 par andar jati hain aur aath second baad aik bachche ko god mein liye bahar aati hain, jo nursery ka wahid bachne wala bachcha hai, phir woh dobara andar jane ki koshish karti hain. Dr. Abdul Rehman 6:39:12 par bahar aate hain. 6:39:15 tak aik camera ka manzar bari had tak dhuen se ojhal ho chuka hota hai; doosra camera 6:40:08 tak ojhal ho jata hai. Committee ne paya ke yeh shawahid sabit karte hain ke agli saf ke amle ne fori taur par bachao ki koshishein kin, aur sarahat se kehte hue ke "lihaza ghair janibdarana shawahid un aam ilzamat ki taeed nahin karte ke agli saf ke tibbi aur nursing amle ne nawzaida bachchon ko mehz chhor diya."

The precise cause of the fire remains technically unresolved. The committee said accounts variously attribute it to an air conditioning unit, an incubator or warmer, or an electrical short circuit or overloaded plug, and that utility company IESCO’s records show no external feeder fault, which shifts the inquiry toward PIMS’s internal wiring and equipment. Maintenance records show several incubators had recently been serviced, though the committee said this does not rule out an equipment-related origin, and it described identifying a specific cause at this stage as premature, pending forensic examination.

A more serious and still-unresolved question concerns how long it took to alert outside help. CCTV places the emergency at approximately 6:38am, but the Capital Emergency Service’s own records show it received its first call about 16 minutes later, at 6:54am, dispatching at 6:55am and arriving at 7:01am. The committee noted that other evidence reportedly refers to an earlier call, a contradiction it has not yet resolved, and said it is examining telephone records, PIMS control room logs, and CES call recordings to establish who first called, when an effective call actually reached emergency services, and whether an avoidable delay occurred. Notably, the report found CES’s own response, from receiving the call to arriving on scene, took only six to seven minutes, meaning the more material issue is not a slow response from CES after being notified, but the internal chain of detection, escalation, and notification that preceded that call. The committee found PIMS’s existing procedures did not clearly establish who was responsible for activating an alarm, summoning emergency services, assuming incident command, or unlocking emergency exits.

On evacuation infrastructure, the committee found PIMS had no approved, trained, or rehearsed fire and evacuation procedure specific to the nursery or neonatal patients, despite having a Security Department SOP dating to May 2023 that explicitly assigned the Assistant Director of Security responsibility for fire exits, firefighting equipment, and staff training. Personnel had even been nominated for fire safety training before the incident, leading the committee to frame the emerging question as whether assigned duties and training were ever translated into actual preparedness. The Capital Emergency Service independently reported that fire and life-safety arrangements were “inadequate and compromised,” that emergency exits were locked or obstructed, and that firefighters were forced to breach locked fire-exit doors to reach the scene, findings the committee called serious but said still require verification of each door’s exact status before individual responsibility can be assigned.

The report places particular weight on a fire that broke out at PIMS’s Female Nursing Hostel on July 6, only seven weeks before the nursery fire. That earlier inquiry had already identified an absence of adequate smoke detection, alarms, documented drills, and fire-safety inspection records, and had recommended a comprehensive fire-safety audit, working smoke detectors, emergency lighting, and annual electrical inspections. In one of the report’s most striking findings, the committee noted that on August 25, the day before the nursery fire, the July inquiry’s own report was still being returned for revision because it had not adequately addressed its terms of reference. The committee was careful to say this does not establish that finishing that inquiry would have prevented the nursery tragedy, but said it shows the institutional process for turning the July fire’s lessons into corrective action had not reached closure before a second, fatal fire occurred.

Based on these findings, the Prime Minister’s Office directed the immediate suspension of eight officials, with disciplinary proceedings launched under the Efficiency and Discipline Rules 2020 and criminal proceedings ordered against those found responsible. On the clinical side, the committee found fewer staff on duty than the roster required and recommended the suspension of Professor Dr. Sadia Riaz, head of the neonatology department, and Senior Registrar Dr. Nagham, holding the department head responsible for ensuring staff presence. On the administrative side, it recommended suspending PIMS Executive Director Professor Dr. Imran Sikandar, Joint Executive Director Dr. Mutahir Shah, Joint Executive Director (Non-Medical) Ch. Waris Ali Raza, and MCH Director Dr. Nosheela Amjad, finding the hospital’s administration failed to act on the lessons of the July fire. On external agencies, it recommended suspending Capital Emergency Service Director-General Dr. Abdul Rehman, finding CES itself failed to press PIMS for drills and protocols even after the July fire, and Assistant Director of Security Muhammad Usman specifically for absence from duty without leave and dereliction of duty. Separately, Charge Nurse Nasreen and Security Guard Maria were placed off-duty pending the committee’s final report, without prejudice either way, while Staff Nurse Razia, who rescued the fire’s only surviving infant, was awarded a cash reward of Rs 10 million and recommended for a civil honour.

The committee also examined the hospital’s private security contractor, M/s Belfort Security Services, finding its personnel had been deployed at the site and had taken part in rescue and firefighting efforts, with no evidence the company caused the fire or that its staff generally abandoned their posts. It nonetheless recommended PIMS verify whether Belfort’s contracted deployment, training, and equipment met its obligations, with any confirmed default to trigger contractual penalties and further action, and referred the matter of Belfort’s licence to the Interior and Narcotics Control Division.

On possible criminal liability, the committee identified two areas it considered potentially serious enough to warrant investigation: confirmed instances of locked or obstructed emergency exits, if the relevant doors are established as mandatory fire exits that specific individuals knowingly or negligently left unavailable, and any confirmed case where officials who received the July fire’s warnings had clear duty and opportunity to fix known hazards but failed to do so without justification. The committee stressed that administrative, contractual, and criminal processes must be kept separate, and that it is identifying circumstances for referral rather than pronouncing guilt itself, which remains a matter for investigating and judicial authorities.

Dr. Muhammad Salman, CEO of the National Institutes of Health, has been transferred to serve as PIMS’s acting executive director on deputation, retaining his NIH role in an additional capacity until a permanent arrangement is made. The Prime Minister’s Office has directed that the interim report be published on the website of the National Health Services, Regulations and Coordination Division.

The committee also ordered a set of immediate corrective measures it said could not wait for its final report. PIMS has been directed to carry out a hospital-wide fire, life-safety, and electrical audit using independent technical expertise, starting with the NICU and nursery, other ICUs, and operating theatres, with every smoke detector, alarm, extinguisher, hydrant, and designated fire exit to be physically inspected, tested, and documented, and any emergency exit found locked, obstructed, or incapable of immediate use rectified without delay. All incubators, warmers, air conditioning units, sockets, wiring, and other electrical systems in high-risk clinical areas are to undergo urgent technical inspection, with temporary fire-watch arrangements put in place wherever automatic detection remains inadequate, alongside practical fire and evacuation drills involving doctors, nurses, security, and engineering staff. The committee also ordered a clear, tested emergency-notification protocol under which a fire triggers a simultaneous internal alarm and direct notification to emergency services, rather than relying on the kind of informal, multi-layered communication chain the report found responsible for the delay in this incident, with a named responsible officer for each step. Every deficiency identified by the July inquiry, past inspections, and this report is to be tracked through a time-bound compliance system naming the responsible officer, the required action, a deadline, and independent verification that it was actually completed. The committee framed the reasoning behind this bluntly: “the July record demonstrates that identifying deficiencies without ensuring implementation does not provide effective institutional protection.”

Some findings remain open. The committee said further verification is needed on how many other staff were actually present in the nursery at the time versus the official roster, and said engineering, electrical, and biomedical personnel require further technical scrutiny before any responsibility can be attributed to them, cautioning that a fire being electrical in origin does not by itself justify blaming those staff. It also examined the corridor door visible on CCTV adjoining the nursery, which was closed until 6:39:45am, after rescue efforts had already begun through another access point, and noted that controlled access to a neonatal unit serves a legitimate security purpose, meaning a locked or restricted door is not by itself evidence of negligence unless it is confirmed as a required emergency exit that materially delayed the response.

The committee said its final report will fix individual responsibility only where the evidence establishes a complete chain connecting a person’s duty, their knowledge of a hazard, their omission, and the resulting harm.

Source:
Prime Minister’s Office directive and Inquiry Committee Interim Report, dated August 28-29, 2026

TT News Desk